Datasheet

Supply voltage at DC rated value 24V
Supply voltage frequency
● rated value
60...50Hz
Operating range factor supply voltage rated value
● at AC at 50 Hz
0.8...1.1
● at AC at 60 Hz
0.8...1.1
● at DC
0.8...1.1
Precision
Relative metering precision 0.1%
Relative linearity deviation 0.05%
Temperature drift per °C 0.015%/°C
Voltage ripple maximum 20mV
Limit frequency 30Hz
Settling time for 1 % deviation 17ms
Rise time 6ms
Main circuit
Type of voltage AC/DC
Inputs/ Outputs
Input voltage 30V
Property of the output Short-circuit proof Yes
Type of signal at input 0 ... 20 mA
Type of signal at output 0 ... 20 mA
Input impedance of current input maximum 100Ω
Outputs
Load
● at the current output maximum
500Ω
Electromagnetic compatibility
EMC emitted interference
● acc. to IEC 60947-1
Environment B
EMI immunity
● acc. to IEC 60947-1
corresponds to degree of severity 3
Conducted interference
● due to burst acc. to IEC 61000-4-4
1 kV 5/50 ns
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Galvanic isolation
Design of the electrical isolation 3 paths
Galvanic isolation
3RS7002-1CE00 Subject to change without notice
Page 2/
6
08/02/2019 © Copyright Siemens