Data Sheet
Data sheet 3RR2243-1FW30
Monitoring relay, can be mounted to Contactor 3RT2, Size S2
standard, digitally adjustable Apparant/active current monitoring
8...80 A, 20...400 Hz, 3-phase Supply 24-240 V AC/DC 1 change-
over contact, 1 semiconductor output for alarm and warning
Monitoring for Current overshoot and undershoot Phase failure,
Cable break Phase sequence Residual current Blocking current
Warning and alarm thresholds with or without fault buffer ON delay 0-
99 s Noise pulse suppression 0-30 s Pause after fault 0-300 min
Screw connection system
Product brand name SIRIUS
Product designation Monitoring relays
Design of the product digitally adjustable, 3-phase current monitoring
Product type designation 3RR2
General technical data
Size of contactor can be combined company-specific S2
Operating apparent output rated value 4V·A
Surge voltage resistance rated value 6kV
Protection class IP
● on the front
IP20
● of the terminal
IP00
Shock resistance 10g / 11 ms
Mechanical service life (switching cycles)
● typical
10000000
Electrical endurance (switching cycles)
● at AC-15 at 230 V typical
100000
Reference code acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
K
Reference code acc. to DIN EN 81346-2 K
3RR2243-1FW30 Subject to change without notice
Page 1/
7
09/11/2019 © Copyright Siemens