Data Sheet

● at 250 V
3A
Operating current of auxiliary contacts at DC-13
● at 24 V
1A
● at 125 V
0.2A
● at 250 V
0.1A
Operating frequency with 3RT2 contactor maximum 50001/h
Contact reliability of auxiliary contacts one incorrect switching operation of 100 million switching
operations (17 V, 5 mA)
Contact rating of auxiliary contacts according to UL R300 / B300
Influence of the surrounding temperature ±5 %
Power supply influence ±1 %
Inputs/ Outputs
Product function
● non-volatile
No
Electromagnetic compatibility
EMI immunity
● acc. to IEC 61812-1
EN 61000-6-2
Conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV network connection / 1 kV control connection
● due to conductor-earth surge acc. to IEC
61000-4-5
2 kV
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV
Field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Safety related data
Protection against electrical shock finger-safe
Type of insulation Basic insulation
Category acc. to EN 954-1 none
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● solid
2x (0,5 ...1,5 mm²), 2x (0,75 ... 2,5 mm²)
● finely stranded with core end processing
2x (0,5 ...1,5 mm²), 2x (0,75 ... 2,5 mm²)
● at AWG conductors solid
2x (18 ... 14)
● at AWG conductors stranded
2x (18 ... 14)
Connectable conductor cross-section
3RP2025-1AP30 Subject to change without notice
Page 4/
6