Datasheet

● at 125 V
0.2A
● at 250 V
0.1A
Main circuit
Operating frequency rated value 50...60Hz
Outputs
Ampacity of the output relay at AC-15
● at 250 V at 50/60 Hz
3A
Ampacity of the output relay at DC-13
● at 24 V
1A
● at 125 V
0.2A
Continuous current of the DIAZED fuse link of the
output relay
6A
Electromagnetic compatibility
Conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV (power ports) / 1 kV (signal ports)
● due to conductor-earth surge acc. to IEC
61000-4-5
2kV (line to ground)
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV (line to line)
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Galvanic isolation
Design of the electrical isolation galvanic isolation
Galvanic isolation
● between entrance and outlet
Yes
● between the outputs
Yes
● between the voltage supply and other circuits
No
Safety related data
Safety Integrity Level (SIL) acc. to IEC 61508 1
Safe failure fraction (SFF) 74%
Failure rate [FIT]
● at rate of recognizable hazardous failures (λdd)
0.0000000681/h
● at rate of non-recognizable hazardous failures
(λdu)
0.000000311/h
PFHD with high demand rate acc. to EN 62061 0.000000381/h
PFDavg with low demand rate acc. to IEC 61508 0.0041
MTBF 97y
MTTFd 303y
Hardware fault tolerance acc. to IEC 61508 0
T1 value for proof test interval or service life acc. to
IEC 61508
3y
Connections/ Terminals
3RN2011-1BA30 Subject to change without notice
Page 3/
7
08/02/2019 © Copyright Siemens