Datasheet

● at 250 V
0.1A
Main circuit
Operating frequency rated value 50...60Hz
Outputs
Ampacity of the output relay at AC-15
● at 250 V at 50/60 Hz
3A
Ampacity of the output relay at DC-13
● at 24 V
1A
● at 125 V
0.2A
Continuous current of the DIAZED fuse link of the
output relay
6A
Electromagnetic compatibility
Conducted interference
● due to burst acc. to IEC 61000-4-4
2 kV (power ports) / 1 kV (signal ports)
● due to conductor-earth surge acc. to IEC
61000-4-5
2kV (line to ground)
● due to conductor-conductor surge acc. to IEC
61000-4-5
1 kV (line to line)
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Galvanic isolation
Design of the electrical isolation galvanic isolation
Galvanic isolation
● between entrance and outlet
Yes
● between the outputs
Yes
● between the voltage supply and other circuits
No
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
Yes
Type of electrical connection screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● solid
1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing
1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG conductors solid
1x (20 ... 12), 2x (20 ... 14)
Connectable conductor cross-section
● solid
0.5...4mm²
● finely stranded with core end processing
0.5...4mm²
AWG number as coded connectable conductor cross
section
● solid
20...12
3RN2010-1CA30 Subject to change without notice
Page 3/
7
08/02/2019 © Copyright Siemens