Datasheet

— at 50 Hz
0.85...1.1
— at 60 Hz
1.1...0.85
Control current
● at AC
— at 230 V
— in standby mode
6mA
— during operation
14mA
— when switching on
25mA
— at 110 V
— in standby mode
8mA
— during operation
25mA
— when switching on
40mA
● at DC
— in standby mode
4mA
— during operation
30mA
— when switching on
13mA
Input voltage at digital input
● for signal <1>
— at DC
79...121V
— at AC
93...253V
● with signal <0>
— at AC
0...40V
— at DC
0...40V
Input current at digital input
● for signal <1>
— at AC at 230 V
2.3mA
— at AC at 110 V
1.1mA
— at DC
1.5mA
● with signal <0>
— at AC at 230 V
0.4mA
— at AC at 110 V
0.2mA
— at DC
0.25mA
Switch-on delay time 90...120ms
OFF-delay time 60...90ms
Auxiliary circuit:
Number of CO contacts for auxiliary contacts 1
Operating current of the auxiliary contacts
● at AC-15 at 230 V maximum
3A
● at DC-13 at 24 V maximum
1A
Installation/ mounting/ dimensions:
mounting position vertical, horizontal, standing
3RM1102-2AA14 Changes preserved
Page 4/
7
22.10.2015 © Copyright Siemens AG