Datasheet
Insulation voltage Rated value 500V
Mechanical service life (switching cycles) typical 30000000
Conducted interference due to conductor-conductor
surge acc. to IEC 61000-4-5
2 kV
Conducted interference due to burst acc. to IEC
61000-4-4
3 kV / 5 kHz
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V
Electrostatic discharge acc. to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Field-bound HF-interference emission acc. to
CISPR11
Class B for the domestic, business and commercial environments
Conducted HF-interference emissions acc. to
CISPR11
Class B for the domestic, business and commercial environments
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
500V
● between control and auxiliary circuit
250V
Equipment marking acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
Q
Equipment marking acc. to DIN EN 61346-2 Q
Safety related data:
Safety Integrity Level (SIL) acc. to IEC 61508 SIL3
Performance level (PL) acc. to EN ISO 13849-1 e
Category acc. to EN ISO 13849-1 4
Safety device type acc. to IEC 61508-2 Type B
Hardware fault tolerance acc. to IEC 61508 1
PFHD with high demand rate acc. to EN 62061 0.000000021/h
PFDavg with low demand rate acc. to IEC 61508 0.000018
T1 value for proof test interval or service life acc. to
IEC 61508
20y
Safe state Load circuit open
Stop category acc. to DIN EN 60204-1 0
Safe failure fraction (SFF) 99.4%
MTTFd 75y
Average diagnostic coverage level (DCavg) 99%
Function test interval maximum 1y
Diagnostics test interval by internal test function
maximum
600s
Failure rate [FIT] at rate of recognizable hazardous
failures (λdd)
1400FIT
Failure rate [FIT] at rate of non-recognizable
hazardous failures (λdu)
16FIT
Protection against electrical shock finger-safe
OFF-delay time with safety-related request when
switched off via control inputs maximum
65ms
3RM1102-2AA04 Changes preserved
Page 2/
6
22.10.2015 © Copyright Siemens AG