Auxiliary circuit:
Number of CO contacts for auxiliary contacts 1
Operating current of the auxiliary contacts
● at AC-15 at 230 V maximum
3A
● at DC-13 at 24 V maximum
1A
Installation/ mounting/ dimensions:
mounting position vertical, horizontal, standing
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
Width 22.5mm
Height 100mm
Depth 141.6mm
Connections/ Terminals:
Type of electrical connection
● for main current circuit
PUSH-IN connection (spring-loaded connection)
● for auxiliary and control current circuit
PUSH-IN connection (spring-loaded connection)
Type of connectable conductor cross-section for
main contacts
● solid
1x (0.5 ... 4 mm²)
● finely stranded
— with core end processing
1x (0.5 ... 2.5 mm²)
— without core end processing
1x (0.5 ... 4 mm²)
Type of connectable conductor cross-section for
AWG conductors for main contacts
1x (20 ... 12)
Type of connectable conductor cross-section for
auxiliary contacts
● solid
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
● finely stranded
— with core end processing
1x (0,5 ... 1,0 mm²), 2x (0,5 ... 1,0 mm²)
— without core end processing
1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²)
Type of connectable conductor cross-section for
AWG conductors for auxiliary contacts
1x (20 ... 16), 2x (20 ... 16)
UL ratings:
Full-load current (FLA) for three-phase AC motor at
480 V Rated value
2A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 230 V Rated value
0.125hp
● for three-phase AC motor
— at 200/208 V Rated value
0.333hp
— at 220/230 V Rated value
0.333hp
— at 460/480 V Rated value
0.75hp
3RM1002-2AA14 Changes preserved
Page 4/
6
22.10.2015 © Copyright Siemens AG