Datasheet

Insulation voltage Rated value 500V
Mechanical service life (switching cycles) typical 30000000
Conducted interference due to conductor-conductor
surge acc. to IEC 61000-4-5
1 kV
Conducted interference due to burst acc. to IEC
61000-4-4
3 kV / 5 kHz
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Field-bound HF-interference emission acc. to
CISPR11
Class B for domestic, business and commercial environments;
Class A for industrial environments at 110 V DC
Conducted HF-interference emissions acc. to
CISPR11
Class B for domestic, business and commercial environments;
Class A for industrial environments at 110 V DC
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
500V
● between control and auxiliary circuit
250V
Equipment marking acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
Q
Equipment marking acc. to DIN EN 61346-2 Q
Safety related data:
Protection against electrical shock finger-safe
Main circuit:
Number of poles for main current circuit 3
Operating voltage Rated value maximum 500V
Relative symmetrical tolerance of the operating
voltage
10%
Operating frequency
● 1 Rated value
50Hz
● 2 Rated value
60Hz
Relative symmetrical tolerance of the operating
frequency
10%
Operating current at AC-53a at 400 V at ambient
temperature 40 °C Rated value
2A
Minimum load [% of IM] 20%
Active power loss typical 0.3W
Adjustable response value current of the current-
dependent overload release
0.4...2A
Operating power for three-phase motors at 400 V at
50 Hz
0.09...0.75kW
Operating frequency maximum 11/s
Control circuit/ Control:
Type of voltage of the control supply voltage AC/DC
Control supply voltage 1
3RM1002-2AA14 Changes preserved
Page 2/
6
22.10.2015 © Copyright Siemens AG