Datasheet
— at 110 V
1A
— at 220 V
0.3A
● with 2 current paths in series at DC-13
— at 24 V rated value
10A
— at 60 V rated value
3.5A
— at 110 V rated value
1.3A
— at 220 V rated value
0.9A
— at 440 V rated value
0.2A
— at 600 V rated value
0.1A
● with 3 current paths in series at DC-13
— at 24 V rated value
10A
— at 60 V rated value
4.7A
— at 110 V rated value
3A
— at 220 V rated value
1.2A
— at 440 V rated value
0.5A
— at 600 V rated value
0.26A
Installation/ mounting/ dimensions
Mounting type snap-on mounting
Width 36mm
Height 41.5mm
Depth 47.7mm
Connections/Terminals
Type of electrical connection for auxiliary and control
current circuit
spring-loaded terminals
Type of connectable conductor cross-sections
● for auxiliary contacts
— finely stranded
— with core end processing
2x (0.5 ... 1.5 mm²)
— without core end processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (20 ... 14)
Safety related data
Product function Mirror contact acc. to IEC 60947-4-1 Yes
● Note
with 3RT2
Product function positively driven operation acc. to
IEC 60947-5-1
Yes
● Note
with 3RH2
Certificates/approvals
3RH2911-2FA22 Subject to change without notice
Page 3/
6
07/25/2019 © Copyright Siemens