Data Sheet
Operating range factor control supply voltage rated
value / at DC
● initial value
0.63
● Full-scale value
1.25
Control current / at minimum control supply voltage
● at DC
2mA
Control current / at DC / rated value 15mA
Number of NC contacts / for auxiliary contacts 0
Number of NO contacts / for auxiliary contacts 0
Number of CO contacts / for auxiliary contacts 0
Installation/ mounting/ dimensions
Mounting position vertical
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
● Side-by-side mounting
Yes
Height 95mm
Width 90mm
Depth 100.8mm
Required spacing / with side-by-side mounting
● upwards
70mm
● downwards
50mm
Installation altitude / at height above sea level /
maximum
1000m
Connections/ Terminals
Product function / removable terminal for auxiliary
and control circuit
Yes
Type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 2.5 mm²)
— finely stranded / with core end processing
2x (0.5 ... 1.5 mm²)
— finely stranded / without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors / for main contacts
2x (18 ... 14)
Type of connectable conductor cross-sections
● for auxiliary and control contacts
— solid
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded / with core end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
— finely stranded / without core end
processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
3RF3416-1BB04 Subject to change without notice
Page 3/
8
09/12/2019 © Copyright Siemens