Data Sheet
Reference code / acc. to DIN 40719 extended
according to IEC 204-2 / acc. to IEC 750
K
Reference code / acc. to DIN EN 81346-2 Q
Reference code / acc. to DIN EN 61346-2 Q
Main circuit
Number of poles / for main current circuit 3
Number of NO contacts / for main contacts 2
Number of NC contacts / for main contacts 0
Operating voltage / at AC
● at 50 Hz / rated value
48...480V
● at 60 Hz / rated value
48...480V
Operating frequency / rated value 50...60Hz
Relative symmetrical tolerance / of the operating
frequency
10%
Operating range relative to the operating voltage / at
AC
● at 50 Hz
40...506V
● at 60 Hz
40...506V
Operating current / minimum 500mA
Operating current
● at AC-3 / at 400 V / rated value
16A
● at AC-53a / at 400 V / at ambient temperature
40 °C / rated value
16A
Operating power
● at AC-3 / at 400 V / rated value
7.5kW
Rate of voltage rise / at the thyristor / for main
contacts / maximum permissible
1000V/µs
Blocking voltage / at the thyristor / for main contacts /
maximum permissible
1200V
Reverse current / of the thyristor 10mA
Derating temperature 40°C
Surge current resistance / rated value 1150A
I2t value / maximum 6600A²·s
Control circuit/ Control
Type of voltage / of the control supply voltage DC
Control supply voltage / 1
● at DC / rated value
24V
Control supply voltage
● at DC / initial value for signal <1> detection
15V
● at DC / Full-scale value for signal<0>
recognition
5V
Symmetrical line frequency tolerance 5Hz
3RF3416-1BB04 Subject to change without notice
Page 2/
8
09/12/2019 © Copyright Siemens