Datasheet
Main circuit:
Number of poles / for main current circuit 3
Number of NC contacts / for main contacts 0
Number of NO contacts / for main contacts 2
Operating frequency
• rated value Hz 60 … 50
Operating voltage
• at 60 Hz / at AC / rated value V 48 … 480
• at 50 Hz / at AC / rated value V 48 … 480
Operating current
• minimum mA 500
• at AC-3 / at 400 V / rated value A 5.4
Working area related to the operating voltage
• at 50 Hz / for AC V 40 … 506
• at 60 Hz / for AC V 40 … 506
Service power / at AC-3 / at 400 V
• rated value kW 2.2
Derating temperature °C 40
Tolerance of the line frequency Hz 5
Relative symmetrical tolerance / of the operation frequency % 10
I2t-level / maximum A²·s 1,800
Voltage slew rate / at the thyristor / for main contacts
• maximum permissible V/µs 1,000
Block voltage / at the thyristor / for main contacts
• maximum permissible V 1,200
Reverse current / of the thyristor mA 10
Control circuit:
Type of voltage / of the controlled supply voltage DC
Control supply voltage
• 1
• for DC
• initial rated value V 15
• final rated value V 24
• for DC / final value for signal<0>-recognition V 5
Control current
• for DC / rated value mA 15
• at minimum control supply voltage / for DC mA 2
Auxiliary circuit:
3RF3405-1BD04
Page 2/ 10/11/2011
subject to modifications
© Copyright Siemens AG 2011
5