Data Sheet

Reference code / acc. to DIN EN 81346-2 Q
Reference code / acc. to DIN EN 61346-2 Q
Main circuit
Number of poles / for main current circuit 1
Number of NO contacts / for main contacts 1
Number of NC contacts / for main contacts 0
Operating voltage / at AC
● at 50 Hz / rated value
48...460V
● at 60 Hz / rated value
48...460V
Operating frequency / rated value 50...60Hz
Operating range relative to the operating voltage / at
AC
● at 50 Hz
40...506V
● at 60 Hz
40...506V
Operating current / minimum 500mA
Operating current
● at AC-1 / at 400 V / rated value
30A
● at AC-51 / rated value
30A
Operating current / of the MCB / at AC / rated value 25A
Rate of voltage rise / at the thyristor / for main
contacts / maximum permissible
1000V/µs
Blocking voltage / at the thyristor / for main contacts /
maximum permissible
1200V
Reverse current / of the thyristor 10mA
Derating temperature 40°C
Surge current resistance / rated value 1150A
I2t value / maximum 6600A²·s
Control circuit/ Control
Type of voltage / of the control supply voltage DC
Control supply voltage / 1
● at DC
77...110V
Control supply voltage
● at DC / Full-scale value for signal<0>
recognition
40V
Control current / at DC / rated value 10mA
Switch-on delay time 1ms; additionally max. one half-wave
Off-delay time 1ms; additionally max. one half-wave
Number of NC contacts / for auxiliary contacts 0
Number of NO contacts / for auxiliary contacts 0
Number of CO contacts / for auxiliary contacts 0
Installation/ mounting/ dimensions
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
3RF2330-2DA64 Subject to change without notice
Page 2/
6
09/13/2019 © Copyright Siemens