Data Sheet
Number of NO contacts / for main contacts 1
Number of NC contacts / for main contacts 0
Operating voltage / at AC
● at 50 Hz / rated value
24...230V
● at 60 Hz / rated value
24...230V
Operating frequency / rated value 50...60Hz
Operating range relative to the operating voltage / at
AC
● at 50 Hz
20...253V
● at 60 Hz
20...253V
Operating current / minimum 500mA
Operating current
● at AC-1 / at 400 V / rated value
20A
● at AC-51 / rated value
20A
Rate of voltage rise / at the thyristor / for main
contacts / maximum permissible
1000V/µs
Blocking voltage / at the thyristor / for main contacts /
maximum permissible
800V
Reverse current / of the thyristor 25mA
Derating temperature 40°C
Surge current resistance / rated value 600A
I2t value / maximum 1800A²·s
Control circuit/ Control
Type of voltage / of the control supply voltage AC
Control supply voltage / 1 / at AC
● at 50 Hz
110...230V
● at 60 Hz
110...230V
Control supply voltage frequency
● 1 / rated value
50Hz
● 2 / rated value
60Hz
Control supply voltage / at AC
● at 50 Hz / Full-scale value for signal<0>
recognition
40V
● at 60 Hz / Full-scale value for signal<0>
recognition
40V
Control supply voltage
● at AC / initial value for signal <1> detection
90V
Symmetrical line frequency tolerance 5Hz
Control current / at minimum control supply voltage
● at AC
2mA
Control current / at AC / rated value 15mA
Switch-on delay time 40ms; additionally max. one half-wave
Off-delay time 40ms; additionally max. one half-wave
3RF2320-2CA22 Subject to change without notice
Page 2/
7
09/13/2019 © Copyright Siemens