Datasheet

Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 0
Number of CO contacts for auxiliary contacts 0
Main circuit:
Number of NO contacts for main contacts 3
Number of NC contacts for main contacts 0
Operating current
● Rated value maximum
A 55
● at AC-51 Rated value
A 20
● minimum
mA 500
Derating temperature °C 40
Surge current resistance Rated value A 600
I2t value maximum A²·s 1800
Operating voltage at AC
● at 50 Hz Rated value
V 48...600
● at 60 Hz Rated value
V 48...600
Operating range relative to the operating voltage at
AC
● at 50 Hz
V 40...660
● at 60 Hz
V 40...660
Operating frequency Rated value Hz 50...60
Relative symmetrical tolerance of the operating
frequency
% 10
Insulation voltage Rated value V 600
Rate of voltage rise at the thyristor for main contacts
maximum permissible
V/µs 100
Blocking voltage at the thyristor for main contacts
maximum permissible
V 1200
Reverse current of the thyristor mA 10
Control current at minimum control supply voltage
● at DC
mA 2
Short-circuit protection, design of the fuse link
Control circuit/ Control:
Type of voltage of the control supply voltage DC
Control supply voltage 1
● at DC
V 4...30
Control supply voltage
● at DC Full-scale value for signal<0> recognition
V 1
Control current
● at DC Rated value
mA 15
Installation/ mounting/ dimensions:
Mounting type screw fixing
3RF22 55-2AC45 Changes preserved
Page 2/
5
23.09.2015 © Copyright Siemens AG