Datasheet

Short-circuit:
Design of the fuse link / for short-circuit protection of the
auxiliary switch
• required fuse gL/gG: 10 A
Installation/mounting/dimensions:
Type of mounting screw and snap-on mounting
Width mm 45
Height mm 170
Depth mm 165
mounting position any
Connections:
Product function
• removable terminal for main circuit Yes
• removable terminal for auxiliary and control circuit Yes
Design of the electrical connection
• for main current circuit screw-type terminals
• for auxiliary and control current circuit screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• solid 2x (1.5 ... 6 mm²), 1x 10 mm²
• finely stranded
• with conductor end processing 2x (1.5 ... 6 mm²)
• for auxiliary contacts
• solid 0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²)
• finely stranded
• with conductor end processing 0.5 ... 2.5 mm², 2x (0.5 ... 1.5 mm²)
• for AWG conductors
• for main contacts 2x (16 ... 10), 1x 8
• for auxiliary contacts 2x (20 ... 14)
Certificates/approvals:
Verification of suitability IEC / EN 60947-6-2
3RA6120-1CB32
Page 4/ 02/26/2013
subject to modifications
© Copyright Siemens AG 2013
7