Datasheet
● acc. to IEC 60068-2-27
6g / 11 ms
Mechanical service life (switching cycles)
● of contactor typical
10000000
Type of assignment 2
Type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
Certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
Protection against electrical shock finger-safe
Ambient conditions
Temperature compensation -20...+60°C
Relative humidity during operation 10...95%
Main circuit
Number of poles for main current circuit 3
Design of the switching contact electromechanical
Adjustable pick-up value current of the current-
dependent overload release
9...12.5A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating frequency rated value 50...60Hz
Operating current
● at AC-3
— at 400 V rated value
11.5A
Operating power
● at AC-3
— at 400 V rated value
5500W
Control circuit/ Control
Type of voltage of the control supply voltage DC
Control supply voltage at DC
● rated value
24V
Holding power of magnet coil at DC 5.9W
Auxiliary circuit
Product extension Auxiliary switch Yes
Protective and monitoring functions
Trip class CLASS 10
Design of the overload release thermal (bimetallic)
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
11A
Yielded mechanical performance [hp]
3RA2120-1KH24-0BB4 Subject to change without notice
Page 2/
7
09/11/2019 © Copyright Siemens