Data Sheet

Auxiliary circuit
Number of connected NC contacts / for auxiliary
contacts
0
Number of connected NO contacts / for auxiliary
contacts
0
Number of connected CO contacts / for auxiliary
contacts
0
Number of CO contacts / for auxiliary contacts 0
Number of NC contacts / for auxiliary contacts 6
Number of NO contacts / for auxiliary contacts 6
Suitability
Suitability for use
● Main switch
Yes
● switch disconnector
Yes
● EMERGENCY OFF switch
Yes
● safety switch
Yes
● maintenance/repair switch
Yes
Product details
Product feature / interlock No
Product component
● Trip indicator
No
● Voltage trigger
No
● undervoltage release
No
● undervoltage release with leading contact
No
Product extension
● Auxiliary switch
Yes
● optional
— motor drive
No
— Voltage trigger
No
Short circuit
Short-circuit current making capacity (Icm)
● for switch disconnector / at 690 V AC/440 V DC
/ without fuse link / rated value / minimum
26kA
● for switch disconnector / without fuse link /
rated value / minimum
26kA
Conditional short-circuit current / with line-side fuse
protection
● at 500 V / by gG fuse / rated value
65kA
Connections
● Type of connectable conductor cross-sections /
for aluminum conductor / stranded / with lug
1x (25 ... 240 mm²), 2x (25 ... 120 mm²)
3KD4040-0PE10-0 Subject to change without notice
Page 4/
9
09/13/2019 © Copyright Siemens