Technical data

Dimensions
28
A B C D E F G H J K L M
130.0
(3,302)
48.0
(1,219)
40.0
(1,016)
4.25
(109)
22.0
(559)
4.0
(102)
7.5
(191)
3.5
(89)
4.25
(109)
43.75
(1,111)
45.68
(1,160)
0.12
(3)
N P Q R S T U V W X Y Z
42.12
(1,070)
2.82
(72)
2.13
(54)
1.16
(29)
45.84
(1,164)
87.06
(2,211)
126.91
(3,224)
6.0
(152)
47.5
(1,207)
96.0
(2,438)
99.0
(2,515)
7.38
(187)
Footnotes:
1
Recommended location of conduits for power cables, top or
bottom.
2
Recommended location of secondary leads, top or bottom.
3
Allow 6” (152 mm) clearance for lift truck on each end.
4
Floor must be level 80” (2,032 mm) in front of switchgear to
allow proper operation of lift truck.
Table 9: Type GM38 switchgear floor plan detail dimensions in inches (mm)
3
Figure 29: Indoor type GM38 switchgear floor plan Figure 30: Outdoor type OGM38 non-walk-in switchgear floor plan
B
B
C
C
D
D
E
E
1
1
22
3,4
3,4
F
F
A
A
J
K
Q
S
K
Q
L
M M
N
P
G
Z
G
P
R
T
U
J
2 2
P P
N
M M