Technical data
Standard accessories include:
  Manual racking crank
  Manual spring charging crank
  Drawout extension rails (facilitate 
handling of circuit breakers in outdoor 
non-walk-in switchgear or drawout fuse 
trucks when located above floor level)
  Lifting sling (for circuit breakers or 
drawout fuse trucks located above floor 
level)
  Split plug jumper (standard unless test 
cabinet is furnished)
   Contact  lubricant
  Touch up paint.
Optional accessories include:
  Lift device (facilitate handling of circuit 
breakers in outdoor non-walk-in 
switchgear or drawout fuse trucks 
when located above floor level)
  Test cabinet (in place of split plug 
jumper)
  Test plugs (if required by devices)
  Electric racking motor assembly (to 
enable racking while operator is at a 
distance from the switchgear)
  Manually or electrically operated 
ground and test device.
Test provisions, either a split plug jumper 
or a test cabinet, are available for testing 
the circuit breaker outside its cubicle.
The split plug jumper is used to bridge 
the secondary disconnects with a flexible 
cable, so the circuit breaker may be 
electrically closed and tripped with the 
control switch on the instrument panel 
while the circuit breaker is outside of its 
compartment. The test cabinet, including 
a control switch, is used for closing and 
tripping the circuit breaker at a location 
remote from the switchgear.
Manually operated ground and test 
device
This is a drawout element that can be 
inserted into a circuit breaker cell. It 
opens the shutters, connects to the cell 
primary disconnecting contacts, and so 
provides a means to make the primary 
disconnect stabs available for testing. It is 
suitable for high-potential testing of 
outgoing circuits of the switchgear main 
bus or for phase-sequence checking. It 
also provides a means to connect 
temporary grounds to de-energized 
circuits for maintenance purposes. Either 
three-stud or six-stud devices are 
available.
Electrically operated ground and test 
device
An electrically operated ground and test 
device includes a power operated switch 
(derived from a type 38-3AH3 circuit 
breaker) arranged to allow grounding 
one set of disconnect stabs. Two devices, 
one each for the upper and lower stabs, 
are required if grounding is desired to 
either side of the unit. The device 
includes test ports to allow for testing for 
presence of voltage on both the line side 
and the load side of the cell. The device 
also provides a means of access to the 
primary circuits for high-potential tests or 
for phase-sequence checking. These 
devices are able to close and latch against 
short-circuit currents corresponding to 
the ratings of the equipment. Due to the 
unique requirements frequently involved 
in such devices, all applications of 
electrically operated ground and test 
devices should be referred to Siemens  
for review.
Note: Each user must develop definitive 
operating procedures for incorporating 
safe operating practices. Only qualified 
personnel should be allowed to use 
ground and test devices.
Accessories
13
Figure 14: Manually operated ground and test device 
with doors open and closed
Figure 15: Electrically operated ground and test 
device










