Technical data
Voltage transformers (VTs)
Up to three VTs with their drawout 
mounted current limiting fuses may be 
mounted in an auxiliary cell. VTs can be 
accommodated in the upper cell above a 
circuit breaker, or in either the upper or 
lower cells of a section that does not 
have a circuit breaker cell.
When the drawout fuses are moved to 
the disconnect position, they are 
automatically disconnected, and the 
transformer windings are grounded to 
remove any static charge. An insulating 
shutter is provided, arranged to operate 
before primary fuses become accessible 
for inspection or removal.
Control power transformers (CPTs)
CPTs can be accommodated in either of 
two manners. For single-phase and small 
three-phase transformers, the primary 
drawout fuses can be located in the 
upper auxiliary cell of a vertical section, 
and the fixed-mounted CPT can be 
located in the lower front cell of the same 
vertical section.
Alternatively, the primary drawout fuses 
can be located in the lower auxiliary cell 
of a vertical section, and the fixed-
mounted CPT can be located in the rear 
of the section.
The secondary molded case breaker is 
interlocked with the drawout primary 
fuses so that the secondary circuit 
breaker must be open before the CPT 
primary can be disconnected or 
connected. 
This prevents accidental load-current 
interruption on the main primary 
contacts. With the secondary molded 
case breaker open and the latch released, 
the primary fuse truck can be moved 
easily to the disconnect position. The 
operation of the drawout fuse truck and 
insulating shutter is similar to that for the 
V Ts.
Current transformers (CTs)
Siemens toroidal CTs comply with ANSI/
IEEE standards and are mounted at the 
rear of the circuit breaker cell. Up to four 
standard accuracy type MD38 or special 
accuracy type MDD38 CTs may be 
mounted on each phase: two on the bus 
side and two on the load side around  
the primary disconnect bushings. CTs 
may be added or changed with the cell 
de-energized without removing bus bar 
or cable connections. Multi-ratio CTs are 
available.
Primary termination compartment 
The primary termination compartment at 
the rear of the switchgear section is 
separated from all other compartments 
by barriers. This space can be used for 
connecting power cables, bus duct or for 
connection to an adjacent power 
transformer (PT). Surge arresters may 
also be provided in this compartment. 
Bolted rear plates are provided as 
standard to provide access to the cable 
area for each unit. Hinged rear doors are 
available as an option.
Infrared (IR) viewing windows are 
optionally available for use in checking 
temperature of conductors in the primary 
termination compartment. 
Bus bar system
Full-round-edge copper bus bar with 
silver-plated joints is standard. Tin-plated 
copper bus is available as an option. High 
strength grade 5 steel hardware with split 
lock washers assures constant pressure, 
low-resistance connections. A 0.25 in.  
(6 mm) x 2.0 in. (51 mm) copper ground 
bus bar is standard in all vertical sections 
and is accessible at each end of the 
lineup and in the primary termination of 
each section. The main bus is available in 
1,200 A, 2,000 A or 3,000 A self-cooled 
ratings. The main bus bar system is 
enclosed by grounded metal barriers.
Construction
10
Figure 7: Primary CL fuses accessible when fuse truck 
in disconnect position and access door open
Figure 8: VT cell with fuse truck withdrawn (shutter
closed, VT primaries grounded)
Figure 9: Fuse truck on extension rails










