Instruction manual
Vehicle function and operational 
interlocks
A type 38-3AH3 vacuum circuit breaker is 
comprised mainly of the vacuum 
interrupter/operator module fitted to a 
vehicle. This vacuum interrupter/operator 
module is an integral arrangement of 
operating mechanism, dielectric system, 
vacuum interrupters and means of 
connecting the primary circuit. The vehicle 
supports the vaccum interrupter/operator 
module, providing mobility and fully 
coordinated application in Siemens type 
GM38 switchgear.
Successful coordinated application of the 
fully assembled type 38-3AH3 vacuum 
circuit breaker is achieved through precise 
alignment in fixtures during manufacture, 
and important functional interlocking.
Alignment
All aspects of the circuit breaker structure 
impacting alignment and 
interchangeability are checked using 
master fixtures at the factory. Field 
adjustment will not normally be required.
Interlocks
Circuit breaker racking-interlocks
The vacuum interrupter/operator module, 
the vehicle portion of the circuit breaker 
and the racking mechanism in the 
switchgear all cooperate to provide 
important operational interlocking 
functions.
1. Rating interlock
 The rating interlock consisting of a 
coded-interference plate is mounted on 
the vehicle (refer to Figure 32: Circuit-
breaker interlocks and ground 
disconnect on page 33). A mating-
interference blocking plate is mounted 
in the drawout compartment (refer to 
Figure 33: Circuit-breaker compartment 
(MOC/TOC switch cover removed for 
photo on page 34). 
When circuit breakers are located above 
floor level, handling of the circuit breakers 
requires the use of a lifting device or a 
crane with a lift sling.
Racking mechanism
Figure 33: Circuit-breaker compartment 
(MOC/TOC switch cover removed for 
photo) on page 34 shows the racking 
mechanism in the switchgear used to 
move the circuit breaker among the 
DISCONNECT, TEST and CONNECT 
positions. This mechanism contains a 
circuit-breaker racking-block that mates 
with the bottom of the circuit-breaker 
housing, and locks the circuit breaker to 
the racking mechanism during in and out 
movement. 
A racking crank (refer to Figure 2: Type 38-
3AH3 vacuum circuit breaker racking on 
page 11) mates to the threaded square-
shaft of the racking mechanism. Clockwise 
rotation of the crank moves the circuit 
breaker into the switchgear, and 
counterclockwise rotation removes it.
The racking and trip-free interlocks provide 
several essential functions.
1. They prevent racking a CLOSED circuit 
breaker into or out of the switchgear 
assembly.
2. They discharge the closing springs 
whenever the circuit breaker is inserted 
into or withdrawn from the switchgear.
3. They prevent closing of the circuit 
breaker unless it is in either the TEST or 
CONNECT positions, and the racking 
crank is not engaged.
The rating interlock prevents insertion of a 
lower-rated circuit breaker into a cubicle 
intended for a circuit breaker of higher 
ratings.
Vacuum interrupter/
operator