Instruction manual
Vacuum interrupter/
operator
Figure 21: Operator sequential operation diagram
Closed 
voltage applied.
Undervoltage device 
27 picks up.
Spring-charge motor 
(88.0) energized.
L3 opens in series 
with anti-pump relay 
(52Y).
LS21 and LS22 
operate to de-
energize spring-
charging motor.
LS4 closes to signal 
closing spring is 
charged.
LS9 closes close 
circuit only when 
closing spring is fully 
charged.
Closing spring is fully 
charged.
No action! Open 52b 
in series with close 
coil (52SRC) blocks 
closing spring-
release.
Close coil is actuated 
through the closed 
52b contacts and the 
two normally closed 
contacts of the anti-
pump relay (52Y).
Closing 
command 
when
circuit 
breaker is 
closed.
circuit 
breaker is 
open.
No action! Anti-
pump relay (52Y) 
picks up through the 
closed LS3 contact 
and opens.
closing 
spring is not 
charged.
The closing spring is 
unlatched.
The opening spring 
is charged.
Circuit breaker 
auxiliary contacts 
52a and 52b change 
state.
The circuit breaker 
closes.
LS21 and LS22 close 
to energize motor 
(88). LS3 closes and 
LS4 opens to cancel 
closing spring signal.
52a contacts in 
series with the trip 
coil (52T) close to 
enable a trip 
opertion.
Continuous 
closing command.
Close coil (52SRC) 
unlatches the closing 
spring and the circuit 
breaker closes.
Motor cutoff 
switches LS21, LS22 
and LS3 are closed 
because the closing 
spring is discharged.
Before the spring-
charge motor has 
recharged the 
closing spring and 
opened LS3, anti-
pump relay (52Y) 
picks up and seals in.
The anti-pump relay 
(52Y) opens two 
contacts in series 
with the close coil 
(52SRC).
The close coil 
(52SRC) is now 
blocked and cannot 
be activated until 
springs are fully-
charged and close 
command is 
removed.
Rapid auto-reclosing. The closing spring is automatically recharged as described above. 
Therefore, when the circuit breaker is closed both of its springs are charged. The closing spring 
charges the opening spring during closing. As a result, the circuit breaker is capable of an 
O-0.3s-CO-3 min-CO operating cycle. The dashed line shows the operating sequence initiated by 
the closing command.
Closing
Tripping
Anti-pumping feature (52Y) assures a continuously applied closing command does not 
cause the circuit breaker to reclose automatically after it has tripped out on a fault.
Trip 
command.
Trip coil (52T) can 
only be activated 
when in series 
connected 52a 
contact is closed.
Undervoltage device (27) is 
activated by opening a NC 
contact in series with 27 or by 
loss or reduction of tripping 
voltage.
1
Secondary shunt-
release (dual-trip) 
function activated by 
remote trip 
command contact 
NO.
1
Undervoltage device (27) is activated 
by closing NO contact, shorting the 
27 coil. The NO contact is only 
effective with the circuit breaker 
closed. Resistor required.
1
Undervoltage device 
27 unlatches the 
opening spring.
1
Circuit breaker trips.
Secondary release 
unlatches the 
opening spring.
1
Trip coil (52T) 
unlatches the 
opening spring.
Footnote:
1
 Optional items.
28