Specifications
7SR242 Duobias Applications Guide
2.10.1 Application with Capacitor Cone Units
Capacitor cones provide a cost effective method of deriving residual voltage. The wide range of capacitor cone
component values used by different manufacturers means that the relay cannot be connected directly to the
cones.
The external adaptor unit contains parallel switched capacitors that enable a wide range of values to be selected
using a DIL switch and hence the Capacitor Cone output can be scaled to the standard relay input range.
2.10.2 Derived NVD Voltage
Alternatively NVD voltage can be derived from the three phase to neutral voltages, this setting is available within
the relay. Note with this method the NVD protection may mal-operate during a VT Fail condition.
©2010 Siemens Protection Devices Limited Chapter 7 Page 36 of 56