Specifications
7SR242 Duobias Applications Guide
W1 Internal Phase-Phase Fault
Figure 2-8: Relay Currents - Star Winding Internal Phase Fault
Notes
B - C fault causes current to flow in the A, B and C elements
The Yd ICT connection causes a 1:2:1 current distribution and introduces a 1/3 multiplying factor.
Relay may indicate three phase fault