Specifications

7SR242 Duobias Applications Guide
2.1.5.1 Example 1 – Further Analysis
Having established settings to ensure stability under load, transient and external fault conditions the following
considers the operating levels for internal faults. The ‘fault setting’ for internal fault conditions is affected by the
ICT Multiplier and ICT Connection settings applied:
W1 Internal Earth Fault
Figure 2-7: Relay Currents - Star Winding Internal Earth
Notes
A- E fault causes current to flow in the A and C elements
The Yd ICT connection reduces current flow by a factor of 1/3
Relay may indicate A and C faults
©2010 Siemens Protection Devices Limited Chapter 7 Page 19 of 56