Specifications

7SR242 Duobias Data Communications
©2010 Siemens Protection Devices Limited Chapter 4 Page 35 of 43
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Static Variation reported when variation 0 requested: 2 (Binary Input 2 with status)
Change Event Variation reported when variation 0 requested: 3 (Binary Input Change with Relative Time)
Point Index Name/Description Default Class Default Variation Default Event Variation
95 46BC-2 2 2 2
96 27/59-1 2 2 2
97 27/59-2 2 2 2
98 27/59-3 2 2 2
99 27/59-4 2 2 2
100 59NIT 2 2 2
101 59NDT 2 2 2
102 81-1 2 2 2
103 81-2 2 2 2
104 81-3 2 2 2
105 81-4 2 2 2
106 81-5 2 2 2
107 81-6 2 2 2
108 24DT-1 2 2 2
109 24DT-2 2 2 2
110 24IT 2 2 2
111 Trip Circuit Fail 1 2 2 2
112 Trip Circuit Fail 2 2 2 2
113 Trip Circuit Fail 3 2 2 2
114 Trip Circuit Fail 4 2 2 2
115 Trip Circuit Fail 5 2 2 2
116 Trip Circuit Fail 6 2 2 2
117 Trip Circuit Fail 7 2 2 2
118 Trip Circuit Fail 8 2 2 2
119 Trip Circuit Fail 9 2 2 2
120 Trip Circuit Fail 10 2 2 2
121 CB1 Total Trip Count 2 2 2
122 CB1 Delta Trip Count 2 2 2
123 CB1 Lockout trip Count 2 2 2
124 I^2t CB1 Wear 2 2 2
125 I^2t CB2 Wear 2 2 2
126 CB2 Total Trip Count 2 2 2
127 CB2 Delta Trip Count 2 2 2
128 CB2 Lockout trip Count 2 2 2
129 General Alarm 1 2 2 2
130 General Alarm 2 2 2 2
131 General Alarm 3 2 2 2
132 General Alarm 4 2 2 2
133 General Alarm 5 2 2 2
134 General Alarm 6 2 2 2
135 General Alarm 7 2 2 2
136 General Alarm 8 2 2 2
137 General Alarm 9 2 2 2
138 General Alarm 10 2 2 2
139 General Alarm 11 2 2 2
140 General Alarm 12 2 2 2
141 Quick Logic E1 2 2 2
142 Quick Logic E2 2 2 2
143 Quick Logic E3 2 2 2
144 Quick Logic E4 2 2 2