Brochure
Table Of Contents
- Table of Contents/TIs
- Pneumatic Room Thermostats-Powerstar
- Pneumatic Room Thermostats- D Series
- Pneumatic Thermostats for Specialized Applications
- Pneumatic Relative Humidity Sensors
- Electric Room Thermostats/Controllers
- Low Voltage Wall Thermostats
- Line Voltage Remote Bulb Thermostats
- Line Voltage Room Thermostats-Heating/Cooling
- RAA... Room Thermostats
- RAB... Fan Coil Thermostats
- RCC... Room Temperature Controllers for 2-pipe Fan Coil Units
- RCC... Free Energy Band Room Temperature Controllers for 4-pipe Fan Coil Units
- RCU50... Room Temperature Controllers for CAV and VAV Systems
- RCU61 Room Temperature Controllers for CAV and VAV Systems
- RDU... Room Temperature Controllers with LCD for Heating/Cooling Systems
- RDX... Room Temperature Controllers with LCD
- Electric Thermostats for Specialized Applications
- Accessories and Service Kits
A-28
Specifications/Product Ordering
Thermostats & Hygrostats
Low Temp.
Part No. 134-1700
Ambient Temperature Range ............................Greater than set point to
140°F (60°C)
Pneumatic Switch ...........................NC, 0.020” (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ..............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish .............................................................. Gray Baked Enamel
Shipping Weight ............................................................2.45 lb. (1.11 kg)
Part No. 134-1710
Ambient Temperature Range .............................................-40 to +140°F
(-40 to +60°C)
Pneumatic Switch .............................NC, 0.02” (0.6 mm) diameter bleed
Control Point Low
Temperature Thermostat ..............................Lowest temperature at any
one foot section of the sensing bulb
Case Finish .............................................................. Gray Baked Enamel
Shipping Weight ........................................................... 2.38 lb. (1.08 kg)
Temperature Maximum Bulb Bulb & Capillary
Range Differential Temperature Length Switch Reclose Part No.
15 to 55°F 5°F (2.8°C) 400°F (204°C) 20’ (6 m) Temperature must 134-1700
(-9 to +12.8°C) with Non-Adjustable increase by 5°F
stop at 35°F (1.67°C) (2.8°C) before
pneumatic switch can
be reclosed.
100 to 170°F 10°F (5.6°C) 250°F (121°C) 2.7” (69 mm) Dia. x Temperature must 134-1710
(38 to 77°C) Non-Adjustable 10” (25.4 cm) L bulb drop 10°F (5.6°C)
with 6’ (183 mm) before pneumatic
capillary switch can be
reclosed.
134
High Temp.
Dimensions in inches (millimeters).
Dimensions
Page
89
Page
89