Brochure

A-22
Specifications/Product Ordering
Thermostats & Hygrostats
Direct Acting
Control Action .............................................................. Direct or Reverse
Maximum Supply Air Pressure ..................................... 30 psi (207 kPa)
Sensitivity Range (adjustable) .............0.25 to 2 psi/°F (3 to 25 kPa/°C)
Factory Sensitivity Setting .................................1.25 psi/°F (15 kPa/°C)
Temperature Response .................................................... 0.50°F (0.9°C)
Dial Graduations ................................................. 5°F (2.7°C)/2°C (3.6°F)
Maximum Ambient Temperature
Case ................................................................................. 200°F (93°C)
Bulb (Direct Acting) ......................................................... 225°F (107°C)
Bulb (Reverse Acting) ..................................................... 250°F (121°C)
Nominal Air Supply Pressure .................. 18 to 25 psi (124 to 172 kPa)
Maximum External Pressure (on bulb) .................... 250 psi (1722 kPa)
Mounting .................................................................... Flange or 3/8” NPT
Air Connections ......................................................................... 1/8” NPT
Dimensions
Bulb Length .......................................................................18” (457 mm)
Flange OD ........................................................................2.56” (65 mm)
Case .......................................................................1.5” Diameter x 3” L
(33 mm Diameter x 76 mm L)
Shipping Weight ............................................................. 2.0 lb. (0.91 kg)
Temperature Operating Range Part No.
0 to 100 °F (-18 to +38°C) 356-0012
30 to 180°F (-1.11 to +82.2°C) 356-0750
-20 to +40°C (-4 to +104°F) 356-0014
0 to 80°C (32 to 176°F) 356-1003
0 to 100°F (-18 to +38°C) 356-0013
30 to 180°F (-1.11 to +82.2°C) 356-1005
100 to 250°F (37.8 to 121°C) 356-1006
-20 to +40°C (-4 to +104°F) 356-0015
0 to 80°C (32 to 176°F) 356-1007
40 to 120°C (104 to 248°F) 356-1008
356 Limitem
Reverse Acting
When using the Limitem as a one-pipe
device, a 40 scim (11 ml/s) restrictor
will limit your output to 80% of supply.
A 20 scim (5 ml/s) restrictor will limit
your output to 60% of supply.
Example: With a 20 scim (5 ml/s)
restrictor and 25 psi (11.3 kPa) supply,
your maximum output is 15 psi
(6.8 kPa).
Page
90
Page