Installation Instructions

Installation Instructions
Document No. 129-131
September 24, 2009
TT 184 Temperature Transmitter
Item Number 129-131, Rev. 200 Page 1 of 4
Product Description
The TT 184 Temperature Transmitter senses
temperature and transmits a proportional pneumatic
signal to a remotely located receiver gauge and/or
receiver-controller.
Product Numbers
Table 1.
Model
Range °F (°C)
(3 -15 psig)
(21 -103 kPa)
Product
Number
Rigid Bulb Transmitter
1/4-inch x 9-inch
(6.4 mm x 229 mm) Bulb
35 to 135°F
(1.7 to 57.2°C)
184-0001
50 to 100° F
(10 to 37.8°C)
184-0002
80 to 240°F
(27 to 116°C)
184-0003
0 to 100°F
(-18 to 37.8°C)
184-0028
Remote Bulb Transmitter
3/32-inch x 20 feet
(2.4 mm x 6.1 m)
Averaging Bulb
12-inch (0.305 m) Capillary
35 to 135°F
(1.7 to 57.2°C)
0 to 100°F
(-18 to 37.8°C)
184-0004
184-0048
Remote Bulb Transmitter
1/4-inch x 4-inch
(6.4 mm x 102 mm) Bulb,
3 foot (0.92 m) Capillary
-40 to 120°F
(-40 to 48.9°C)
184-0005
50 to 100°F
(10 to 37.8°C)
184-0018
80 to 240°F
(27 to 116°C)
184-0014
0 to 100°F
(-18 to 37.9°C)
184-0036
-10 to 65°F
(-23 to 18°C)
184-0015
35 to 135°
(1.7 to 57.2°C)
184-0034
Remote Bulb Transmitter
1/4-inch x 4-inch
(6.4 mm x 102 mm) Bulb,
3 ft. (0.92 m) Armored
Capillary
-40 to 120°
(-40 to 48.9°C)
184-0006
Room Transmitter
(with 180-443A Wall Plate
and 192-256 Cover)
50 to 100°F
(10 to 37.8°C)
184-0340
Table 2. Accessories.
Description Model Product Number
Well mounting
bracket kit
Remote Bulb
184-105
Copper well
Remote Bulb
184-119
Stainless steel well
Remote Bulb
184-118
Outdoor bulb shield
Remote Bulb
929-043
Spring clip mtg. kit
Room Transmitter
182-685
Tubing kit
Room Transmitter
180-896
Troubleshooting
Table 3. Troubleshooting Chart.
Complaint Check Probable
Cause
Corrective
Action
Low
temperature
indication
Restrictor
Plugged
restrictors
Clean and replace
if clogged
Wrong size
restrictor
Replace restrictor
gauge
temperature
indication
vs.
temperature
at sensing
Receiver
gauge out of
calibration
Adjust receiver
gauge
Fittings and
Leak in
transmitter line
As necessary
Dirty Filter
Replace filter
Supply
Low supply
pressure
As necessary
High
temperature
indication
gauge
temperature
indication
vs.
temperature
at sensing
Receiver
gauge out of
calibration
Adjust receiver
gauge
Restrictor
used
More than one
restrictor used.
Both internal
(in receiver-
controller)
restrictor and
external
restrictor
installed
Remove all but
one restricted air
supply
Defective
gasket on
receiver-
controller
restrictor
Replace restrictor
Wrong size
restrictor
Replace restrictor

Summary of content (4 pages)