Installation Instructions
Document No. 129-504
Installation Instructions
June 18, 2019
Page 4 of 8 Siemens Industry, Inc.
Wiring Diagrams
Schémas de raccordement
Diagramas de cableado
Figure 5. GQD12x.1P 2-Position:
24 Vac/dc
Class III
Figure 6. GQD13x.1P Floating:
24 Vac/dc
Class III
Figure 7. GQD15x.1PModulating:
24 Vac/dc
Class III
Figure 8. GQD22x.1U2-Position:
120 Vac
Auxiliary Switches
Actuator
Position
Switch A
Common S1
Connected to
Switch B
Common S4
Connected to
0° to 5°
S3
S6
5° to 85°
S2
S6
85° to 90°
S2
S5
CAUTION:
Mixed switch operation to the switching outputs of both dual end switches (5° and 85°)
is not permitted.
Either AC line voltage from the same phase must be applied to all six outputs of the
fixed dual end switches, or UL-Class 2 voltage must be applied to all six outputs.