Data Sheet for Product
Technical Instructions  OpenAir® Non-Spring Return Rotary Electric Damper Actuator 
Document Number 155-187P25  24 Vac – Modulating Control 
May 13, 2021 
Page 2  Siemens Industry, Inc. 
Specifications 
Power Supply 
Operating voltage (G–G0)  24 Vac +20%, -15% 
Frequency  50/60 Hz 
Power consumption   3.3 VA 
Control signal 
Input signal (Y-G0) 
Voltage-input  0 to 10 Vdc 
  Input resistance >100K ohms 
Feedback signal 
Position output signal  (U–G0) 
(GDE161.1T and GDE161.1N do not have feedback signals) 
Voltage-output   0 to 10 Vdc 
  Maximum output current DC 1 mA 
Equipment rating  
Rating   Class 2 according to UL, CSA 
  Class III per EN60730 
Auxiliary features 
Control signal adjustment 
Offset (start point)   Between 0 to 5 Vdc 
Slope (span)   Between 2 and 30 Vdc 
Dual auxiliary switch contact rating  4A resistive, 2A inductive 
Voltage  24 Vac/24 Vdc 
  DC rating  12 to 30 Vdc 
   DC 2A 
Switch Range 
Switch A    0 to 90° with 5° intervals 
  Recommended range usage   0 to 45 ° 
  Factory setting  5° 
  Switch B  0 to 90° with 5° intervals 
  Recommended range usage   45° to 90° 
  Factory setting   85° 
  Switching hysteresis:  2° 
Function 
Torque 
  GDE  44 lb-in (5 Nm) 
  GLB  88 lb-in (10 Nm) 
Runtime for 90° opening or closing 
  GDE  90 sec. at 60 Hz (108 sec. at 50 Hz) 
  GLB  125 sec. at 60 Hz (150 sec. at 50 Hz) 
Nominal angle of rotation  90° 
Maximum angular rotation   95° 
Mounting 
Shaft size: Minimum shaft length 3/4-inch (20 mm) 
Figure 1. Acceptable Shaft Sizes. 