Installation Instructions
Installation Instructions 
Document No. 129-367 
May 13, 2021 
OpenAir® Electronic Damper Actuator 
GDE/GLB Rotary Non-spring Return 
a.  Actuator 
b.  Position indicator 
c.  Mounting bracket 
d.  Mounting screws 
e.  4 mm hex key 
f.  Shaft insert for use with 
3/8-inch (8-10 mm) shafts 
Item Number: 129-367, Rev. EA  Page 1 of 7 
Figure 1. Parts of the GDE/GLB Rotary Actuator. 
Product Description 
Steps for direct-coupled mounting of the OpenAir 
GDE/GLB Series non-spring return rotary electronic 
damper actuator. 
Product Numbers 
GDE131.1U 
GLB131.1P 
GDE131.1U/B (24 pk) 
GLB136.1P 
GDE131.1P 
GLB161.1P 
GDE131.1P/B (24 pk) 
GLB166.1P 
GDE161.1P 
GDE161.1P/B (24 pk) 
GDE163.1P 
GDE164.1P 
GDE166.1P 
Required Tools 
•  4 mm hex wrench 
•  4 mm (5/32-inch) drill bit and drill 
•  Small, flat-blade screwdriver 
•  Marker or pencil 
Estimated Installation Time 
30 minutes  
Warning/Caution Notations 
WARNING: 
Personal injury or loss of life 
may occur if you do not follow 
a procedure as specified. 
CAUTION: 
Equipment damage or loss of 
data may occur if you do not 
follow a procedure as 
specified. 
Instructions 
WARNING: 
Do not open the actuator. 
NOTE:  Place the actuator on the damper shaft so 
that the front of the actuator is accessible. 
The label is on the front side.  
1.  Determine whether the damper blades will rotate 
clockwise or counterclockwise to open. See 
Figure 2. 
2.  If the blades will rotate counterclockwise, slide the 
manual override switch to manual, and move the 
adjustment lever to the right. Return the switch to 
automatic. See Figure 9. 
To mount a (modulating) GDE/GLB16x, set the Dual 
In-line Package (DIP) switches to the required 
positions. 
1.  To access the DIP switches, raise the tab on the 
lower left side of the actuator. See Figure 2. The 
factory setting is clockwise (middle switch), with a 
direct-acting feedback signal (right switch). 
2.  Close the tab over the DIP switches. 
To mount a (3-position) GDE/GLB13x for counter-
clockwise rotation, follow the Counterclockwise 
Damper Rotation instructions located in the Wiring 
Diagrams section when wiring the actuator to the 
controller. 