Data Sheet for Product

Technical Instructions OpenAir® Non-Spring Return Rotary Electric Damper Actuator
Document Number 155-187P25 24 Vac Modulating Control
May 13, 2021
Page 14 Siemens Industry, Inc.
Wiring, Continued
Post Header AMP
GDE161.1N
The GDE161.1N Post Header AMP has two sets of identical contacts as shown in
Figure 27.
All wiring must conform to NEC and local codes and regulations.
Use earth ground isolating step-down Class 2 transformers. Do not use
autotransformers.
Determine the supply transformer rating by summing the total VA of all actuators
used. It is recommended that one transformer power no more than 12 actuators.
WARNING:
Installations requiring Conformance
All wiring for CE rated actuators must only be separated extra low
voltage (SELV) or protective extra low voltage (PELV) per HD384-4-41.
Use safety-isolating transformers (Class III transformer) per EN 61558.
They must be rated for 100% duty cycle.
Over current protection for supply lines is maximum 10A.
CAUTION:
It is necessary that the output current properly sustain and operate all
GDE161.1N actuators in a daisy chain configuration.
Figure 27. GDE161.1N Post Header AMP.
Figure 28. GDE161.1N 0 to 10 Vdc Modulating Control Wiring Diagram.
NOTE:
You must select
either the top 3
contacts or the
bottom 3 contacts.