Data Sheet for Product
599 Series 6-Way Ball Valves  Technical Instructions 
  Document Number 155-803 
  November 10, 2020 
Siemens Industry, Inc.  Page 7 
Operation, 
Continued 
The Siemens 6-way Ball Valve has an internal pressure equalization function that 
ensures the safe operation of heated and chilled ceilings in a closed valve state (45° 
position). Changes to media temperature in the heated and chilled ceiling can result in 
over or under pressure in a closed state and may even damage part of the heated and 
chilled ceiling. The safety function only acts in the closed valve position (45°). The 
heating and cooling circuits are safely separated while operating. 
Flow Direction 
Ensure that the valve is installed with both media sources piped with proper flow 
direction. Flow direction is indicated on the bib tag that ships with each 6-way ball valve 
and is shown below. See Figure 5. 
AS = Supply from Source A  CS = Supply to Coil  BS = Supply from Source B 
AR = Return to Source A  CR = Return from Coil  BR = Return to Source B 
C
V
A = C
V
 for Source A    C
V
B = C
V
 for Source B 
Figure 5. Flow Direction. 
To illustrate the information in the Operation and Flow Direction sections above, Figure 
6 shows the Source A and Source B flow curves versus the actuator rotation and 
control signal voltage for part numbers 599-10601-1.5-2.9 and 171C-10601-1.5-2.9. In 
this example, the C
V
 of Source A (C
V
A) is 1.5, and the C
V
 of Source B (C
V
B) is 2.9. 
Figure 6.  Example Control Characteristic Curve for 599-10601-1.5-2.9 
and 171C-10601-1.5-2.9. 