Data Sheet for Product
OpenAir® Non-Spring Return Rotary Electric Damper Actuator  Technical Instructions 
24 Vac – Modulating Control  Document Number 155-187P25 
  May 13, 2021 
Siemens Industry, Inc.    Page 11 
Manual Override 
To move the damper blades and lock the position with no 
power present: 
1.  Slide the red manual override knob toward the back of 
the actuator. 
2.  Make adjustments to the damper position. 
3.  Slide the red manual override knob toward the front of 
the actuator. 
Once power is restored, the actuator returns to automated 
control. 
Figure 22.  
Manual Override. 
Mechanical 
Range 
Adjustment 
To mechanically limit the range of the damper blade.  
1.  Loosen the stop set screw. 
2.  Move the screw along the track to 
the desired position, and fasten it 
in place.  
Figure 23. Moving the Mechanical Range Stop. 
To use the entire 0 to 10V input signal to control the mechanically limited range, see 
Figure 18 for setting self-adaptive features. 
Example: 
Stop set screw at 70° 
Self-adapt switch ON 
Input signal Y = 5 Vdc 
The damper will be at 35° (50% of the adjusted range.) 
NOTE:  On versions with the slope and offset features, this example assumes 
    Offset Uo = 0 Vdc 
    Slope U = 10 Vdc 
1 