Data Sheet for Product
Technical Instructions  OpenAir® Non-Spring Return Rotary Electric Damper Actuator 
Document Number 155-187P25  24 Vac – Modulating Control 
May 13, 2021 
Page 16  Siemens Industry, Inc. 
Wiring, Continued 
Daisy Chain 
Configuration,  
Figure 31.  
WARNING:  
Do not configure more than 12 actuators in 
a daisy chain at any time. 
Troubleshooting 
WARNING: 
Do not open the actuator. 
If the actuator is inoperative, replace the unit.  
Start-Up/ 
Commissioning 
1.  Check that the wires are connected correctly. 
2.  Check that offset and slope are set correctly, if used. 
3.  Check that the direction of rotation switch/cable matches the rotation of the damper 
shaft. 
4.  Connect wires 1 (red) and 2 (black) to a Digital Multimeter (DMM) with the dial set at 
AC V to verify that the operating voltage is within range. 
Check operation: 
1.  Connect wires 1 (red) and 2 (black) to the actuator. 
2.  Set the DMM dial to Vdc. 
3.  Connect wires 2 (black) and 8 (gray) to the DMM. 
4.  Apply a full-scale input signal (10 Vdc) to wire 8 (gray). 
5.  Allow the actuator shaft coupling to rotate from 0 to 90°. 
6.  Disconnect wire 8 (gray) and the shaft coupling returns to the “0” position. 
Check Feedback: 
1.  Set the DMM dial to Vdc. 
2.  Attach wires 2 (black) and 9 (pink) to the DMM. 
3.  Apply a full-scale input signal to wire 8 (gray). The reading at the DMM should increase. 
4.  Remove the signal from wire 8 (gray). The reading at the DMM should decrease and 
the actuator shaft coupling returns to the “0” position. 
Check the Auxiliary Switch A: 
1.  Set the DMM dial to ohms (resistance) or continuity check. 
2.  Connect wires S1 and S3 to the DMM. 
The DMM should indicate open circuit or no resistance. 
3.  Apply a full-scale input signal to wire 8 (gray). The DMM should indicate contact closure 
as the actuator shaft coupling reaches the setting of switch A. 
4.  Connect wires S1 and S2 to the DMM. The DMM should indicate open circuit or no 
resistance. 
NOTE: 
You must select either 
the top 3 contacts or the 
bottom 3 contacts. 