Operation 
The parabolic shape of the flow characterizer orifice (Figure 2) provides a slowly 
opening valve. Equal movements of the valve stem, at any point of the flow range, 
change the existing flow an equal percentage regardless of the existing flow. The ball 
valve equal percentage flow characteristic (Figure 3) mirrors the flow characteristic of a 
coil, resulting in linear heat transfer.  
Figure 2. Ball Valve Flow 
Characterizer.  
Figure 3. Ball Valve Equal Percentage  
Flow Control.  
Mounting and 
Installation 
Install the valve so that the flow follows the 
direction of the arrow cast on the valve 
body. 
For added flexibility, the actuator mounting 
plate can be installed in any of the four (4) 
rotation angles relative to the valve body. 
For best performance, install the valve 
assembly with the actuator above the 
valve body.  
The valve and actuator assembly can be 
installed in a horizontal pipe in any position 
between vertical and 90°.  
The ball valve also can be installed 
vertically. 
CAUTION: 
Do not install the valve assembly 
so that the actuator is below 
horizontal or upside-down. 
See Ball Valve Bracket Kit 
Installation Instructions 129-496 
for complete and proper 
installation and mounting 
instructions. 
Allow sufficient space for servicing the 
valve and actuator. See Figure 6 and 
Table 14 for valve body dimensions and 
service envelope. 
Figure 4. Mounting Positions.  
Service 
Replace the valve or actuator if inoperable. 