User Manual
9 / 13
Siemens Switzerland Ltd DS02 Update: http://www.siemens.com/gamma-td
Building Technologies Divison
International Headquarters
Theilerstrasse 1a Siemens AG 2018
6300 Zug Subject to change December 2018
Mounting
The device is intended to be used for permanent interior installations in dry locations within
distribution boards or small casings with DIN rail EN 60715-TH35-7.5.
Mounting and connection
Step 1 Step 2 Step 3
Dismounting
Commissioning
The learning button is used to switch between different operational modes.
Press and hold <2 s:
• Enable addressing mode. The programming LED is on. After receiving a physical address,
the dimmer returns to normal mode.
• Return to normal mode from other modes. (Programming LED is off).
Press and hold >5 s and <20 s:
Enable connection test for commissioning with Desigo.
Press and hold >20 s:
Reset the dimmer to factory settings. Programming LED flashes 8 s.
Note: All configurations are lost. The building site function is re-activated.
Fig. 5 Mounting and connection
Fig. 6 Dismounting