User Manual
6 / 13
Siemens Switzerland Ltd DS02 Update: http://www.siemens.com/gamma-td
Building Technologies Division
International Headquarters
Theilerstrasse 1a Siemens AG 2018
CH-6300 Zug Subject to change December 2018
Notes
Security
DANGER
• The device must be mounted and commissioned by an authorized electrician.
• A safety disconnection of the device must be possible.
• The device must not be opened.
• Use only loads that allow dimming operations.
• Conventional transformers may be used. If they comply with the relevant standards and
contain a thermal fuse.
• For planning and construction of electric installations, the relevant guidelines, regulations
and standards of the respective country are to be considered.
• Connecting inductive loads together with capacitive or resistive loads to the same
dimmer output is not permitted and leads to damage or destruction of the universal
dimmer!
• Dimming of inductive loads with trailing edge mode could damage the device.
Notes
Indication LED
The channel A/B LED indicates the status and error messages.
Indicator
Description
Off
Device is not
powered
by KN
X.
Red, on
Channel output is turned on.
Green, on
Channel output is turned off.
Orange, 0.2 Hz
Channel failure / power failure
Orange, 0.5 Hz
Over
temperature: temperature too high
Orange, 1 Hz
Over
load
: load to
o
high
Orange, 5 Hz
Short circuit:
cu
rrent
to
o
high
Note:
• In case of exceeded temperature, overload, or short circuit, the dimmer turns off the
output. Restart the dimmer by using an “on” or “dimming value > 0” command.
• In case of overtemperature, wait at least 1 minute and then restart the dimmer (cool-
ing down time).
Note:
• Trailing edge mode occurs sometimes with a limited dimming range and an irregular
dimming curve, but with less power-loss. Manual adjustment of control mode (trailing
/leading edge) or min./max. dimming value is possible by Software.