Engineering notes
Installation manual TRA, CM111043, contains all information required to engineer
the KNX PL-Link bus (topology, repeater, etc.)
The PL-Link I/O Block is operated on AC 230 V power. The device directly
supplies power to actuators (valves, dampers). As a result, no separate AC 24 V
supply is required for the field devices.
The sizing and fusing of the power lines are oriented to overall load and local
regulations.
Supply circuits are interrupted as soon as plug 19/21 is removed from the device.
(Bridges 19-19 and 21-21 are located on the print, not the plug; see terminal
diagram page 11).
The power lines must be fused on the device with strain relief.
The potential-free relay outputs allow for switching loads
Up to AC 250 V, 10 A (1.8 kW) (Q14, electric heating release).
Up to AC 250 V, 5 A (4 A) (Q34, fan release).
The sizing and fusing of the power lines are oriented to overall connected load
and local regulations. The switching circuits must be externally fused ( 10 A);
no internal fusing.
The lines must be fused on the device with strain relief.
STOP
Caution!
Electric heaters MUST be equipped with a seperate safety thermostat
The DC 0 … 10 V outputs YC1, YC2 supply max 1.5 mA.
The AC 24 V output G (next to YC2) supplies max. 6 VA.
The DC 0 … 10 V output YC3 supplies max 1.5 mA.
The outputs are inactive
The device is in Backup mode
After a timeout (2 x heartbeat time) the outputs go to Backup value
The field devices (valve and damper actuators are supplied directly by the PL-
Link I/O Block). Separate AC 24 V supply is required only if the field devices
consume more than 6 VA.
Active sensors and actuators with AC 24 V supply: The admissible cable length
is calculated based on a max. voltage drop of 7% (1.68 V) of the AC 24 V supply
voltage at the sensor/actuator.
Active sensors and actuators with A/DC 24 V supply: The admissible cable
length is calculated based on a max. voltage drop of 1% (0.24 V) for actors and
0.5% for active sensors..
See the notes on active sensors and actors in the TRA installation guide,
CM111043.
For time critical functions as light and blinds, use KNX PL-Link pushbuttons.
D1..D4 are not suitable for these purposes because of the low sampling rate.
Power lines
AC 230 V
Potential-free
relay outputs
AC 230 V
DC 0...10 V outputs
Actuators
Fan control
Behavior without a pro
-
cess value (power
-on,
missing
KNX PL-Link
communication
AC 24 V supply for field
devices (G)
Cable length for field
devices with
AC/DC 24 V supply
Digital inputs