Label
ID-number
(Unique serial number)
Barcode for ID, Code 128
Serial number
Test date, series
(Z, A, B, C ...)
Observe notes in this document
Temperature range
(0 ... 50 °C)
Protective category
All connection terminals are plug-in terminals. The terminals are separated to
prevent faulty wiring for terminals connected to AC 230 V (supply, relay outputs).
STOP
Note
Warning!
Cable strain relief for lines for terminals 19 ... 28
(AC230 V) is mandatory. Attach the lines to the
related lugs on the housing base using cable
blinders (see picture, right).
Plug-in terminals connected to power must be
removed from power prior to plug-in or plug-out!
3873J04
The PL-Link I/O Block RXM39.1 contains the following interfaces:
• KNX PL-Link terminals.
• RJ45 tool plug for FW upgrade (proprietary, a Siemens connection cable is
required).
Warning!
• Only trained electrical installation staff may connect the tool plug (RJ45)!
Adjacent terminal may be powered.
• Do not connect Ethernet to the RJ45 plug! The device at the other end might be
destroyed!
Disposal
The devices are considered electronics devices for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as domestic
garbage.
• Dispose of the devices through channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Connection terminals
Communication