User Manual

3 / 14
Siemens RXM39.1 - PL-Link I/O Block CM2N3836en_06
Building Technologies 2016-05-19
The Service LED (3-color) indicates the device's operating status as follows:
Continuously OFF No power supply
Nothing to indicate.
Flashing 1 (1/4 s On, 7/4 s Off)
Feedback for medium button pressure
(yellow)
Feedback during process (yellow)
Flashing 2 (1s On, 1 s Off)
No device detection (red)
Continuously ON
Programming mode (red)
Success (green)
The device carries out the following commands from the service button:
Button pressure
Action
Short (< 0.5 s) Switch on/off programming mode
Do not indicate connection test result
(0.5...2.s)
No action
Medium
(2...20 s)
Start connection test
Long (> 20 s)
Start reset to factory settings
Operation and display interaction:
Short Medium Long
Indication time *)
Button pressure
Indication / success
Failure
Status Programming mode Connection test Reset
Result Factory settings
*) Indication time = 60 s; can be ended by briefly pressing the button.
Warning!
Only trained electrical installation staff may press the service button when the
terminal cover is removed!
Adjacent terminal may be powered.
The device is supplied without terminal covers protecting the connection terminals
against touch and soiling. The service LED is visible also with installed terminal
cover. The service button is pressed using a tool. Remove the cable entry glands
to connect cables to the room automation station.
80049
Remove terminal cover
Service LED
Service button
HMI concept
Terminal cover