User Manual
9 / 12
Siemens PXC....D PXC...-E.D + PXA40-… – Automation stations modular series CM1N9222en_17
Smart Infrastructure 2020-12-03
Connection terminals and interfaces
PXC....D
24 V~
T
CLA
CLB
HMI
HMI
HMI / TOOL
(A)
(B)
(C)
(E)
(F)
(G)
9222Z10
1 2 3
4 5
PXC...-E.D
24 V~
T
HMI
9222Z11
(A)
(D)
(F)
(G)
1 2 3
1, 2
24 V ~, ⊥
Operating voltage AC 24 V
Plug-in screw terminal block
3
Functional ground
(A)
USB host interface (for modem via PXA-C3 adapter cable)
4,5 (B)
CLA, CLB
LONWORKS bus Plug-in screw terminal blocks
(C)
HMI
RJ45 interface (LONWORKS) for operator unit PXM20 (tool as well)
(D)
RJ45 interface for Ethernet
(Operator unit PXM20-E can be connected to hub/switch)
(E)
HMI / Tool
RJ45 interface (LONWORKS and serial) for PXM10, PXM20 and tool
(F)
USB device interface (for future applications)
(G)
HMI
RJ45 interface (serial) for operator unit PXM10