User Manual

Table Of Contents
Logische I/O
-
Bausteine
Adressierungseingaben für PXC...-U, PTM und P-Bus
19
CM110664de_07 291 | 361
Desigo
PX
Kompakt
PXC10-TL
1
PXC12
PXC12-T
PXC22
PXC22-T
PXC36
PXC36-T
PXC52 Signalty
p
Modul Kanal Modul Kanal Modul Kanal Modul Kanal Modul Kanal
Uni-
versal
Inputs
(UI: für
AI, DI)
1 1…4 1 1…6
X1…X6
1 1…8
X1…X8
1 1…12
X1…X12
1 1…16
X1…X16
R1K,
U10, D20
T1, P1K,
N1K
Digital
Inputs
(DI)
(Counter
Input)
2 1…4 2 1…4
D1…D4
2 1…4
D1…D4
2 1…4
D1…D4
D20, C
Digital
Inputs
(DI)
3 1…4 3 1…8
D5…D12
3 1…12
D5…D16
D20
Analog
Outputs
(AO)
- - 4 1…4
Y1…Y2
4 1…4
Y1…Y4
4 1…6
Y1…Y6
4 1…8
Y1…Y8
Y10S
Digital
Outputs
(DO)
5 1…2 5 1…2
51…54
5 1…6
51…56
5 1…8
51…58
5 1…12
51…62
Q250
Hand-
schalter
2
(nur
PXC36-
S)
7 1…4 D_M3
LEDs 8 2…5 8 2…7 Q_LED
Info-LED 8 1 8 1 8 1 8 1 8 1 Q_LED
PPS-2-
Signal
3
3
1..5
3
1..5
3
1..5
3
1..5
3
1..5 R1K,
U10, D20
PXC52
ab
Desigo
V5
4
:
Universal
Inputs /
Outputs
1
4
1…16
X1…X16
1…8
Y1…Y8
D20, C
R1K,
U10, D20
T1, P1K,
N1K,
Y10S
Legende
1
Bei PXC10-TL werden die beiden Taster Alarm1/2 und die beiden DIL-Schalter1/2 auf die Module mit der Adresse 3
abgebildet.
2
Die Handschalter können nur in die Applikation eingelesen werden, wenn die DIL-Schalter (im Deckel des PXC36-S) richtig
gesetzt sind.
3
Syntax für PPS-2 Signal: Q=Raumgerätenummer.Objektnummer (Profilnummer). Es können fünf Geräte angeschlossen
werden.
4
Die bisherigen UI und AO können alle als AI, DI, CI oder AO konfiguriert werden.
Signaltyp wenn keine Applikation geladen ist (Wiring Test): X1...X16 = Y10S, Y1...Y8 = R1K.
Modul 4
Bei Modul 4 steuern die Universalausgänge (UO für AO und DO) einerseits stetige Aktoren (AO) an,
andererseits sind diese auch als binäre Schaltbefehle (DO) verwendbar.
Analoger Ausgang = 0 …10 Volt
Binärer Ausgang = 0 oder 24 Volt DC, max. 22 mA mit Verwendung eines zusätzlichen externen Relais.
Gehäuselayout von PXC52 mit den Adressierbereichen