User Manual

Table Of Contents
Compatibility of Desigo V6.2 Update 3 with
PXC4 and PXC5
25
CM110664en_07 349 | 351
25 Compatibility of Desigo V6.2 Update 3 with PXC4 and
PXC5
Overview
Online system Desigo V6.2 Update 3 with PXC4 and PXC5
Full BACnet communication between the Desigo CC management platform and the Desigo V6.2 Update
3 system.
Full BACnet communication between the Desigo CC management platform and the Desigo PXC4 and
PXC5 system.
BACnet communication between Desigo V6.2 Update 3 and Desigo PXC4 and PXC5: Via COV's.
For system limits of Desigo V6.2 Update 3, see Compatibility [ 334].
For system limits of Desigo PXC4 and PXC5, see
PXC4 & PXC5 Planning Overview
(A6V11973797).
Prerequisites for extending Desigo V6.2 Update 3 (XWP project) with PXC4 and
PXC5
Upgrade the management platform Desigo CC to V4.1.
Make sure all PXC00...200..D primary controllers and room automation products adhere to the Desigo
V6.2 Update 3 compatibility.
You are using Desigo Xworks Plus (XWP) V6.2.
You are using ABT Site V4.0.
Engineering of Desigo V6.2 Update 3 projects with PXC4 and PXC5
Network topology
Structure the network topology as follows: