User Manual
Table Of Contents
- 1 Cyber security disclaimer
- 2 Preconditions of this document
- 3 System overview
- 4 Desigo workflow, tools and programming
- 4.1 Coverage of the technical process
- 4.2 Coverage of the system
- 4.3 Main tasks
- 4.4 Tools for different roles
- 4.5 Working with libraries
- 4.6 Working in parallel and subcontracting
- 4.7 Workflow for primary systems
- 4.8 Workflow for room automation classic
- 4.9 Workflow for Desigo room automation
- 4.10 Desigo Configuration Module (DCM)
- 4.11 Desigo Xworks Plus (XWP)
- 4.12 Desigo Automation Building Tool (ABT)
- 4.13 Programming in D-MAP
- 5 Control concept
- 6 Technical view
- 7 Global objects and functions
- 8 Events and COV reporting
- 9 Alarm management
- 9.1 Alarm sources
- 9.2 Alarm example
- 9.3 Effects of BACnet properties on alarm response
- 9.4 Alarm response of the function blocks
- 9.5 Alarm functions
- 9.6 Alarm management by notification class
- 9.7 Alarm routing over the network
- 9.8 Alarm queuing
- 9.9 Common alarms
- 9.10 Alarm suppression
- 9.11 Alarm message texts
- 10 Calendars and schedulers
- 11 Trending
- 12 Reports
- 13 Data storage
- 14 Network architecture
- 15 Remote access
- 16 Management platform
- 17 Desigo Control Point
- 18 Automation stations
- 19 Logical I/O blocks
- 20 Room automation
- 21 Desigo Open
- 22 System configuration
- 22.1 Technical limits and limit values
- 22.2 Maximum number of elements in a network area
- 22.3 Desigo room automation system function group limits
- 22.4 Devices
- 22.4.1 PXC..D automation stations / system controllers
- 22.4.2 LonWorks system controllers
- 22.4.3 Automation stations with LonWorks integration
- 22.4.4 PX Open integration (PXC001.D/-E.D)
- 22.4.5 PX Open integration (PXC001.D/-E.D + PXA40-RS1)
- 22.4.6 PX Open integration (PXC001.D/-E.D + PXA40-RS2)
- 22.4.7 PX KNX integration (PXC001.D/-E.D)
- 22.4.8 TX Open integration (TXI1/2/2-S.OPEN)
- 22.4.9 Number of data points on Desigo room automation stations
- 22.4.10 Number of data points for PXC3
- 22.4.11 Number of data points for DXR1
- 22.4.12 Number of data points for DXR2
- 22.4.13 PXM20 operator unit
- 22.4.14 PXM10 operator unit
- 22.4.15 Desigo Control Point
- 22.4.16 PXG3.L and PXG3.M BACnet routers
- 22.4.17 SX OPC
- 22.4.18 Desigo CC
- 22.4.19 Desigo Insight
- 22.4.20 Desigo Xworks Plus (XWP)
- 22.4.21 Desigo Automation Building Tool (ABT)
- 22.5 Applications
- 23 Compatibility
- 23.1 Desigo version compatibility definition
- 23.2 Desigo system compatibility basics
- 23.2.1 Compatibility with BACnet standard
- 23.2.2 Compatibility with operating systems
- 23.2.3 Compatibility with SQL servers
- 23.2.4 Compatibility with Microsoft Office
- 23.2.5 Compatibility with web browsers
- 23.2.6 Compatibility with ABT Go
- 23.2.7 Compatibility with VMware (virtual infrastructure)
- 23.2.8 Compatibility of software/libraries on the same PC
- 23.2.9 Hardware and firmware compatibility
- 23.2.10 Backward compatibility
- 23.2.11 Engineering compatibility
- 23.2.12 Compatibility with Desigo Configuration Module (DCM)
- 23.2.13 Compatibility with Desigo PX / Desigo room automation
- 23.2.14 Compatibility with Desigo RX tool
- 23.2.15 Compatibility with TX-I/O
- 23.2.16 Compatibility with TX Open
- 23.3 Desigo Control Point
- 23.4 Upgrading from Desigo V6.2 Update (or Update 2) to V6.2 Update 3
- 23.5 Siemens WEoF clients
- 23.6 Migration compatibility
- 23.7 Hardware requirements of Desigo software products
- 24 Desigo PXC4 and PXC5
- 25 Compatibility of Desigo V6.2 Update 3 with PXC4 and PXC5
Room automation
Desigo room automation
20
CM110664en_07 299 | 351
● TXM1.6R: Relay module for up to 6 data points.
● TXM1.8U: Universal module for up to 8 data points.
See
TX-I/O Assortment overview
(CM2N8170).
Compact room automation stations
Communication
BACnet/IP DXR2.E09
-101A
DXR2.E09
T-101A
DXR2.E10
-101A
DXR2.E12
P
DXR2.E18
-1..A
BACnet MS/TP DXR2.M09
-101A
DXR2.M09
T-101A
DXR2.M10
-101A
DXR2.M11
-101A
DXR2.M12
P
DXR2.M18
-1..A
Housing
DIN
• • •
Flat
• • •
Operating voltage
230V
• • •
24V
• • •
Inputs and outputs onboard
Digital inputs
1 1 1 1 1 2
Universal inputs
2 2 2 2 2 4
Relay outputs
3 1 3
Triac outputs
4 4 6 6 8
Analog outputs (DC 0...10 V)*
3 1 2 2 4
Pressure sensor
1
Maximum configuration
Number of I/O data points
30 30 30 30 30 60
Integrated power supply for KNX (mA)
50 50 50 50 50 50
Key
1
Total number of data points used by TX-I/O, KNX PL-Link and DALI. For details, see chapter
System Configuration
.
PXC3.E16A room automation station for lighting
The PXC3.E16A room automation station is tailored for challenging lighting applications. All lighting
applications that also run on the PXC3.E7.. are available. The PXC3.E16A communicates via BACnet/IP
with the DXR2.E.. and PXC3.E.. room automation stations. Using the on-board DALI interface, up to 64
ECGs (electronic control gear) can be integrated in 16 groups. The PXC3.E16A can be used for centralized
lighting automations or, as applicable, as a supplement to a decentralized HVAC installation.
Example: Centralized lighting installation with decentralized HVAC installation
● DXR2.E.. to automate HVAC in the room
● Centralized installation with PXC3.E..A for lighting