User Manual

Table Of Contents
Room automation
Desigo room automation
20
CM110664en_07 297 | 351
See Range Description
Desigo Room Automation (BACnet), Programmable Room Automation - Emergency
Lighting
(A6V10640596),
Programmable Room Automation - Room Operation
(A6V10640597),
Programmable Room Automation - Distributed Functions and Scenes
(A6V10640598) and
Programmable
Room Automation - Lighting Controls and DALI
(A6V10640599).
Topology
Applications
A comprehensive block library for room automation is provided as part the scope of delivery. The library
contains predefined application functions for room climate, lighting, shading, and superimposed room
functions. The applications can be combined with operating and display functions as required. The
individual application functions can be adapted to customer needs and are programmable. The application
functions do not depend on the selected field devices.
See
Application Catalog
.
Configuration of application functions
Many application functions are preconfigured and available in the library. Retroactive configuration during
engineering or commissioning is possible. Your own configured application functions and entire rooms can
be stored in a project library.
Configuration of field devices
The application architecture does not depend on the field device interface. Field devices can be connected
directly to the PXC3 room automation station (via TX-I/O modules) or via bus (KNX or DALI) or IP
communication.
Many field devices are preconfigured and available in the library. Retroactive configuration during
engineering or commissioning is possible. Project-specific field devices configured accordingly can be
saved in a project library.
Modular room automation stations
PXC3 room automation stations with control functions for one or multiple rooms:
Assume control functions for one or multiple rooms.
Communicate with each other or other system components via BACnet/IP. Scope and functionality of
supported BACnet objects are matched to the requirements of room automation.
Provide a 2-port Ethernet interface for cost-effective cabling via daisy chaining.
Contain bus supplies for island bus, KNX PL-Link, and DALI. Internal bus supplies can be extended for
island bus and KNX PL-Link as needed.
Have an integrated web server for IP communication with QMX7.E38 touch room operator units.
See
Room automation station PXC3.E7..
(CM1N9203) and
Touch room operator unit QMX7.E38
(CM1N9295).
°C
°C
°C
°C
Detector
PXC3.E7..
Modular
TX-I/O-
Modules
DALI
Third-party
devices
Push button
QMX3...
Room operator units
PXC00-E.D
AQR25..
Room sensor
QMX7.E38
Touch operator units
DXR2.E..
Compact AC 24 V
DXR2.E..
Compact AC 230 V
PXC3.E16A
Lighting
DALI
Third-party devices
RXM21/39.1
PL-Link I/O boxes
DXR2.M..
Compact AC 230 V
RS/RL
Modules
Third-party
integration
Third-party
integration
Detector
AQR25..
Room sensor
RS/RL
Modules
Detector
AQR25..
Room sensor
Detector
Push button
AQR25..
Room sensor
Detector
AQR25..
Room sensor
QMX3...
Room operator units
Third-party
integration
Desigo CC
Desigo Control Point
DXR1
iValve
DXR1
BACnet/IP
KNX
KNX
BACnet MS/TP
K
N
X
Ethernet
PXG3.L
Router
DXR2.M..
Compact
AC 230 V
RS/RL
Modules
RS/RL
Modules
RS/RL
Modules
°C
°C
Push button
QMX3...
Room operator units
°C
°C
Push button
QMX3...
Room operator units
°C
°C
Push
button
QMX3...
Room operator units