Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
CM110664en_07 277 | 351
Signal type positioning Description Standard measuring range [Slpe] [Icpt]
Y10S DC 0…10 V 0 10 V 1000 0
PPS2 interface
Transfer of an analog control command to a room unit connected via the PPS2 interface. Only Object 195
(= Room temperature display) can be used in the analog output block. As the value is already available as a
converted or referenced value, no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as
0.
Line resistance with [Icpt]
For analog inputs (measurement of temperatures or resistances), most signal types are calibrated at a line
resistance of 1 Ohm. The [Icpt] can be changed at the AI block if the line resistance deviates strongly from
1 Ohm.
Measuring resistances (internal resolution = 1/10 Ohm):
Line resistance [Slpe] [Icpt]
P1K (Pt1000)
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.0259740
0.0259740
0.0259740
0.0259740
-259.480519
-259.740260
-260.000000
-260.259740
0
0
0
0
0.259740
0
-0.259740
-0.519481
R2K5
P1K (0...2500 Ohm)
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.1
0.1
0.1
0.1
1
0
-1
-2
0
0
0
0
1
0
-1
-2
R250
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
1
0
-1
-2
0
0
0
0
1
0
-1
-2
R250
P100 (0...250 Ohm)*
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0
-1
-2
-3
0
0
0
0
0
-1
-2
-3